PC100-2 Specifications

Control Technique : PID Algorithm with Fuzzy Autotune of PID coefficients

Sensor Inputs : 2 Isolated Factory Selectable RTD, J, K, T Thermocouple, Solid State, Current &Voltage probes (Field configurable within same probe type)

Other Inputs : 2 TTL, One 5V 8 bit A/D, External Failsafe.

Process Outputs : 8 Open Collector 100mA on/off Pulse Width Modulated Outputs.

Two 0 to 5V Outputs : One for Chart Recorder, and One for Process Control.

Remote Control : IEEE-488, RS232, RS422/485

Programmable Set Temp & Time : Number of set temperature and set times limited only by available program memory, typically 100+ segments

Programming : 1 to 65,535 FOR/NEXT loop executions for 10 loops, nesting supported

Resolution : 15 bit Conversion (0.02 Deg C typ.)

Absolute Error after calibration : +/- 0.05 %

Probe Error Compensation : Automatic Cold Junction and Lead Compensation

Long Term Stability (per month) : +/- 0.025 %

Supply Voltage : 110 / 220 +/- 10% ( Selectable at I/O board ), 50/60 Hz

Power Consumption : 10 Watts

Safety Features

Sensor Malfunction : Open / Short probe detect

Controller Malfunction : Hardware Watchdog

Process Errors : External Failsafe input

Process Limits : Software Upper/Lower/Deviation Limits

Line Voltage Loss : Battery-backed memory & TOD clock, Auto Restart after power loss

User Interface : Front Panel - 20 key, 32 character LCD, I/O board - all I/O Ports

Dimensions : 3.81"H x 3.81"W x 6.62"D, 1/4 DIN