Sensor Inputs : 2 Isolated Field Selectable RTD. J, K, T Thermocouples, Solid State, Current & Voltage ( Add 8 Isolated J, K, or T Thermocouples or 4 RTD Probes with SCANNER Option )
Other Inputs : Two TTL, One 5V 8bit A/D, External Failsafe.
Process Outputs : 8 Open Collector 100mA on/off Pulse Width Modulated Outputs.
Two 0 to 5V Outputs : One for Chart Recorder, and One for Process Control.
Control Technique : PID Algorithm
Remote Control : IEEE-488, RS232, RS422/485
Programmable Set Temp & Time : 1 to 65,535 FOR/NEXT loop executions for 10 loops, nesting supported
Resolution : 15 bit Conversion (0.02 Deg C typ.)
Probe Range Accuracy
Absolute Error Over Range : (not including probe error)
RTD : -200 Deg to 325 Deg C +/- 0.2 Deg C
J & K Narrow : -200 Deg to 325 Deg C +/- 0.35 Deg C
J & K Wide : -200 Deg to 760 Deg C +/- 0.5 Deg C
T Thermocouple : -200 Deg to 325 Deg C +/- 0.2 Deg C
Solid State : -60 Deg C to 160 Deg C +/- 0.2 Deg C
Voltage : 0 to 5 Volts +/- 500 uV
Current : 0 to 20 mA +/- 2 uA
Probe Error Compensation : Automatic Cold Junction and Lead Compensation
Electrical Isolation : 240 Volts
Supply Voltage : 110 / 220 +/- 10% ( Selectable at rear panel ), 50/60 Hz
Power Consumption : 35 Watts
Safety Features
Sensor Malfunction : Open / Short probe detect
Controller Malfunction : Hardware Watchdog
Process Errors : External Failsafe input
Process Limits : Software Upper/Lower/Deviation Limits
Line Voltage Loss : Battery-backed memory & TOD clock, Auto Restart after power loss
User Interface : Front Panel - 32 key, 32 character LCD, Rear Panel - all I/O Ports
Dimensions : 3.5"H x 16.5"W x 15"D, 19" rack mountable