PC1000 Specifications

Sensor Inputs : 2 Isolated Field Selectable RTD. J, K, T Thermocouples, Solid State, Current & Voltage ( Add 8 Isolated J, K, or T Thermocouples or 4 RTD Probes with SCANNER Option )

Other Inputs : Two TTL, One 5V 8bit A/D, External Failsafe.

Process Outputs : 8 Open Collector 100mA on/off Pulse Width Modulated Outputs.

Two 0 to 5V Outputs : One for Chart Recorder, and One for Process Control.

Control Technique : PID Algorithm

Remote Control : IEEE-488, RS232, RS422/485

Programmable Set Temp & Time : 1 to 65,535 FOR/NEXT loop executions for 10 loops, nesting supported

Resolution : 15 bit Conversion (0.02 Deg C typ.)

Probe Range Accuracy

Absolute Error Over Range : (not including probe error)

RTD : -200 Deg to 325 Deg C +/- 0.2 Deg C

J & K Narrow : -200 Deg to 325 Deg C +/- 0.35 Deg C

J & K Wide : -200 Deg to 760 Deg C +/- 0.5 Deg C

T Thermocouple : -200 Deg to 325 Deg C +/- 0.2 Deg C

Solid State : -60 Deg C to 160 Deg C +/- 0.2 Deg C

Voltage : 0 to 5 Volts +/- 500 uV

Current : 0 to 20 mA +/- 2 uA

Probe Error Compensation : Automatic Cold Junction and Lead Compensation

Electrical Isolation : 240 Volts

Supply Voltage : 110 / 220 +/- 10% ( Selectable at rear panel ), 50/60 Hz

Power Consumption : 35 Watts

Safety Features

Sensor Malfunction : Open / Short probe detect

Controller Malfunction : Hardware Watchdog

Process Errors : External Failsafe input

Process Limits : Software Upper/Lower/Deviation Limits

Line Voltage Loss : Battery-backed memory & TOD clock, Auto Restart after power loss

User Interface : Front Panel - 32 key, 32 character LCD, Rear Panel - all I/O Ports

Dimensions : 3.5"H x 16.5"W x 15"D, 19" rack mountable

Home