TC01 Specifications
Sensor Inputs : 1 Factory Selectable RTD. J,K, &T Thermocouple, Solid State, Current & Voltage
Process Outputs : Cool Solenoid - 1A @ 240 V, Heater Control - 25A @ 240 V
Auxiliary Outputs ( Compressor ) : 2 TTL open collector with pullup
Control Technique : PID Algorithm, PWM control
Remote Control : IEEE-488, RS232
Number of Scan Set Temps & Times : 10
Set Time-at-Temp Range : 1-1800 minutes or continuous
Resolution : 0.1 Deg C
Absolute Error over Temperature Range : +/- 0.4 Deg C
Probe Error Compensation : Automatic Cold Junction and Lead Compensation
Long Term Stability (per month) : +/- 0.2 Deg C
Supply Voltage : 110 / 220 ( Jumper configured ), 50/60 Hz
Power Consumption : 35 Watts
Sensor Malfunction : Open / Short probe detect
Controller Malfunction : Hardware Watchdog
Process Limits : Software Upper/Lower Limits
User Interface : Front Panel - 16 key, 4 digit LED display
Dimensions : 9"H x 4.75"W x 4.5"D
User Interface : Front Panel - 20 key, 32 character LCD, I/O board - all I/O Ports
Dimensions : 9"H x 4.75"W x 4.5"D