TC02 Specifications
Sensor Inputs : 1 Field Selectable RTD. J,K, &T Thermocouple, Solid State, Current & Voltage
Other Inputs : 2 TTL, One 5V 8 bit A/D, External Failsafe.
Process Outputs : 8 Open Collector 100mA on/off Pulse Width Modulated Outputs. Two 0 to 5V Outputs : One for Chart Recorder, and One for Process Control.
Control Technique : PID Algorithm
Remote Control : IEEE-488, RS232
Programmable Set Temps & Time : Number of set temperatures and set times limited only by available program memory, typically 100+ segments.
Programming : 1 to 65,535 FOR/NEXT loo executions for 10 loops, nesting supported
Resolution : 15 bit Conversion (0.02 Deg C typ.)
Absolute Error after calibration : +/- 0.25 Deg C
Probe Error Compensation : Automatic Cold Junction and Lead Compensation
Long Term Stability (per month) : 0.2 Deg C
Supply Voltage : 110 / 220 +/- 10% ( Selectable at I/O board ), 50/60 Hz
Power Consumption : 35 Watts
Safety Features
Sensor Malfunction : Open / Short probe detect
Controller Malfunction : Hardware Watchdog
Process Errors : External Failsafe input
Process Limits : Software Upper/Lower/Deviation Limits
Line Voltage Loss : Battery-backed memory & TOD clock, Auto Restart after power loss
User Interface : Front Panel - 20 key, 32 character LCD, I/O board - all I/O Ports
Dimensions : 9"H x 4.75"W x 4.5"D